Rockwell Automation 56AMXN ControlLogix/AutoMax/Communication/Module User Manual

Page 19

Advertising
background image

DCSNet/RE RIO Module

19

Publication 56AMXN-IN002A-EN-P November 2002

Hazardous Location information

The following information applies when operating this equipment in hazardous
locations:

The 56AMXN is NOT suitable for use in hazardous locations.
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations

only. Each product is supplied with markings on the rating nameplate indicating the
hazardous location temperature code. When combining products within a system,

the most adverse temperature code (lowest “T” number) may be used to help
determine the overall temperature code of the system. Combinations of equipment

in your system are subject to investigation by the local Authority Having Jurisdiction
at the time of installation.

EXPLOSION HAZARD
• Do not disconnect equipment unless power has been

removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless

power has been removed or the area is known to be

nonhazardous.
Secure any external connections that mate to this

equipment by using screws, sliding latches, threaded
connectors, or other means provided with this product.
• Substitution of components may impair suitability for

Class I, Division 2.
• If this product contains batteries, they must only be

changed in an area known to be nonhazardous.