Rockwell Automation 56AMXN ControlLogix/AutoMax/Communication/Module User Manual

Page 14

Advertising
background image

14

DCSNet/RE RIO Module

Publication 56AMXN-IN002A-EN-P November 2002

Check Power Supply and Module Status

The rack power supply indicator should be green.
The module OK LED should be solid red, then solid green.
The alphanumeric display shows the following messages at powerup.

Alphanumeric Status Display Powerup Messages

B#nn

Boot

Stages in the startup processes

56AMXN Ver
1.xx.xx

Module firmware version

Troubleshooting the Power Supply

If the alphanumeric indicator on the 56AMXN/B module does not cycle through

these messages on powerup, refer to the following table and to the Troubleshooting
section that follows.

Power Supply Indicator

If the POWER
indicator is:

Power Supply Status is

Recommended Action:

Off

Not operating

Turn power switch ON.

Check power wiring
connections.

Check fuse.

On

Operating

None, normal operation.