Page 10

Advertising
background image

Publication 20B-IN021B-EN-P

10

PowerFlex 700 Power Jumpers

Frame

Vo

lt

ag

e

Code

Cur

rent

Rating

Factory Default Jumper Settings

Power Source Type

MOV

(1)

DC Bus Common
Mode Caps &
Input Filter Cap

7

All

All

A green/yellow
wire connected to
Power Terminal
Block “PE”

Not Applicable

Solid Ground
• The green/yellow MOV jumper wire

should be connected to “PE.”

Non-Solid Ground
• The green/yellow MOV jumper wire

should be insulated from ground. If
necessary, remove the wire from “PE”
and insulate/secure it to guard against
unintentional contact with chassis or
components.

8…9

All

All

A green/yellow
wire connected to
the “PE” bus bar

Not Applicable

Solid Ground
• The green/yellow MOV jumper wire

should be connected to “PE.”

Non-Solid Ground
• The green/yellow MOV jumper wire

should be insulated from ground. If
necessary, remove the wire from the
“PE” bus bar and insulate/secure it to
guard against unintentional contact
with chassis or components.

10

All

All

A green/yellow
wire connected to
chassis

Not Applicable

Solid Ground
• The green/yellow MOV jumper wire

should be connected to the chassis.

Non-Solid Ground
• The green/yellow MOV jumper wire

should be insulated from ground. If
necessary, remove the wire and
insulate/secure both ends to guard
against unintentional contact with
chassis or components.

(1)

AC input drives only. MOV’s do not exist on DC input drives.

+DC

USE 75

°

COPPER WIRE ONLY

TORQUE LARGE TERMINALS TO 10 N-m (87LB-IN)

-DC

PE

PE

R-L1

T-L3

RISK OF SHOCK
REPLACE AFTER

SERVICING

!

DANGER

U-M1

V-M2

W-M3

S-L2

TB11

25 AMPERES RMS

MAXIMUM

ALLEN-BRADLEY

MADE IN U.S.A.

PE

MOV

PE

V

W

U

R

S

T

DC-

DC+

GND

MOV

(under boards)

PE Bus

Bar

120
IN1

120
IN2

3

4

5

6

TB10

8 AMPERES RMS

MAXIMUM

GND

RISK OF SHOCK
REPLACE AFTER

SERVICING

!

DANGER

MOV

Jumper Wire

Converter Section