Rockwell Automation 20B PowerFlex 700 Power Jumpers User Manual
Page 10
Publication 20B-IN021B-EN-P
10
PowerFlex 700 Power Jumpers
Frame
Vo
lt
ag
e
Code
Cur
rent
Rating
Factory Default Jumper Settings
Power Source Type
MOV
(1)
DC Bus Common 
Mode Caps & 
Input Filter Cap
7
All
All
A green/yellow 
wire connected to 
Power Terminal 
Block “PE” 
Not Applicable
Solid Ground
• The green/yellow MOV jumper wire 
should be connected to “PE.”
Non-Solid Ground
• The green/yellow MOV jumper wire 
should be insulated from ground. If 
necessary, remove the wire from “PE” 
and insulate/secure it to guard against 
unintentional contact with chassis or 
components. 
8…9
All
All
A green/yellow 
wire connected to 
the “PE” bus bar
Not Applicable
Solid Ground
• The green/yellow MOV jumper wire 
should be connected to “PE.”
Non-Solid Ground
• The green/yellow MOV jumper wire 
should be insulated from ground. If 
necessary, remove the wire from the 
“PE” bus bar and insulate/secure it to 
guard against unintentional contact 
with chassis or components. 
10
All
All
A green/yellow 
wire connected to 
chassis
Not Applicable
Solid Ground
• The green/yellow MOV jumper wire 
should be connected to the chassis.
Non-Solid Ground
• The green/yellow MOV jumper wire 
should be insulated from ground. If 
necessary, remove the wire and 
insulate/secure both ends to guard 
against unintentional contact with 
chassis or components. 
(1)
AC input drives only. MOV’s do not exist on DC input drives.
+DC
USE 75
°
COPPER WIRE ONLY
TORQUE LARGE TERMINALS TO 10 N-m (87LB-IN)
-DC
PE
PE
R-L1
T-L3
RISK OF SHOCK
REPLACE AFTER
SERVICING
!
DANGER
U-M1
V-M2
W-M3
S-L2
TB11
25 AMPERES RMS
MAXIMUM
ALLEN-BRADLEY
MADE IN U.S.A.
PE
MOV
PE
V
W
U
R
S
T
DC-
DC+
GND
MOV
(under boards)
PE Bus
Bar
120
IN1
120
IN2
3
4
5
6
TB10
8 AMPERES RMS
MAXIMUM
GND
RISK OF SHOCK
REPLACE AFTER
SERVICING
!
DANGER
MOV
Jumper Wire
Converter Section