PowerFlex 700 Power Jumpers

5

Publication 20B-IN021B-EN-P

Fra

m

e

Vo

lt

ag

e

Code

C

u

rrent

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input Filter
Caps

(1) (2)

DC Bus Common
Mode Caps

5

B
C
D
H

J

N
P
R

All

except

C140

Two green/yellow
wires connected
to the Power
Terminal Block rail

Green/yellow wire
is connected to
ground

Solid Ground
1. CM Cap jumper wire should be

connected to ground with a metal screw.
Verify.
• Newer Drives - If necessary, remove

the nylon screw/spacer and insert a
metal M5 x 8 screw. Torque to 3.2
N•m (28 lb•in).

• Older Drives - Remove the I/O

Cassette (see User Manual for
details). The green/yellow CM Cap
jumper wire is located on the back of
chassis and should be connected to
ground with a metal screw. If
necessary, remove the insulation
from the wire terminal and connect to
chassis with a metal M5 x 12 screw.
Torque screw to 3.2 N•m (28 lb•in).

2. MOV/Input Filter Cap jumper wires

should be connected to ground with a
metal screw. Verify. If necessary, remove
the nylon screw/spacer and insert a
metal M5 x 12 screw.

Non-Solid Ground
1. CM Cap jumper wire should be insulated

from ground. Verify.
• Newer Drives - If necessary, remove

the metal screw and insert a M5 x 15
nylon screw/spacer.

• Older Drives - Remove the I/O

Cassette (see User Manual for
details). If necessary, insulate/secure
jumper wire to guard against
unintentional contact with chassis or
components.

2. MOV/Input Filter Cap jumper wires

should be insulated from ground with a
nylon screw/spacer. Verify. If necessary,
remove the metal screw and insert a M5
x 20 nylon screw/spacer.

Frame 5 continued on next page

(1)

AC input drives only. MOV’s and input filter caps do not exist on DC input drives.

(2)

When removing MOV’s, the input filter capacitor must also be removed.

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

CM Cap -

Older Drives

MOV / Input Filter Cap

MOV

CM Cap - Newer Drives

Advertising