Rockwell Automation 20B PowerFlex 700 Power Jumpers User Manual
Page 7
PowerFlex 700 Power Jumpers
7
Publication 20B-IN021B-EN-P
Frame
Vo
lt
ag
e
Code
Cur
rent
Rating
Factory Default Jumper Settings
Power Source Type
MOV/Input Filter 
Caps
(1) (2)
DC Bus Common 
Mode Caps
5
NEMA/UL Type 12 Drives
C
D
P
R
All
Two green/yellow 
wires connected 
to chassis ground
Green/yellow wire 
is connected to 
ground
Solid Ground
1. CM Cap jumper wire should be 
connected to ground with a metal screw. 
Verify. 
• Newer Drives - If necessary, remove 
the nylon screw/spacer and insert a 
metal M5 x 8 screw. Torque to 3.2 
N•m (28 lb•in).
• Older Drives - Remove the
I/O Cassette (see User Manual for 
details). The green/yellow CM Cap 
jumper wire is located on the back of 
chassis and should be connected to 
ground with a metal screw. If 
necessary, remove the insulation 
from the wire terminal and connect 
to chassis with a metal M5 x 10 
screw. Torque screw to 3.2 N•m (28 
lb•in). 
2. MOV/Input Filter Cap jumper wires
should be connected to ground with a 
metal screw. Verify. If necessary, 
remove the nylon screw/spacer and 
insert a metal M5 x 12 screw. 
Non-Solid Ground
1. CM Cap jumper wire should be 
insulated from ground. Verify.
• Newer Drives - If necessary, remove 
the metal screw and insert a M5 x 15 
nylon screw/spacer.
• Older Drives - Remove the
I/O Cassette (see User Manual for 
details). If necessary, insulate/
secure jumper wire to guard against 
unintentional contact with chassis or 
components. 
2. MOV/Input Filter Cap jumper wires
should be insulated from ground with a 
nylon screw/spacer. Verify. If necessary, 
remove the metal screw and insert a M5 
x 20 nylon screw/spacer.
Frame 5 continued on next page
(1)
AC input drives only. MOV’s and input filter caps do not exist on DC input drives.
(2)
When removing MOV’s, the input filter capacitor must also be removed.
USE 75 C CU WIRE ONLY
WIRE RANGE: 4-3/0 AWG (18-70 MM2)
TORQUE: 133 IN-LB (15 N-M)
STRIP LENGTH: 1.02 IN (26 MM)
POWER & DC TERMINAL RATINGS
WIRE RANGE: 14-1/0 AWG (2.5-50 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
BRAKE TERMINAL RATINGS
WIRE RANGE: 6-1/0 AWG (18-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)
GROUND TERMINAL RATINGS (PE)
OUTPUT
INPUT AC
300 VDC EXT PWR SPLY TERM (PS+, PS-)
WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)
DANGER
DANGER
RISK OF ELECTRIC
SHOCK AND DEATH
FIELD INSTALLED OPTIONS
6 MM HEX KEY
6 MM HEX KEY
SHLD
SHLD
MOV
MOV / Input Filter Cap
CM Cap -
Older Drives
CM Cap - Newer Drives