Rockwell Automation 20B PowerFlex 700 Power Jumpers User Manual

Page 6

Advertising
background image

Publication 20B-IN021B-EN-P

6

PowerFlex 700 Power Jumpers

Fra

m

e

Vo

lt

ag

e

Code

C

u

rrent

Ra

ti

ng

Factory Default Jumper Settings

Power Source Type

MOV/Input Filter
Caps

(1) (2)

DC Bus Common
Mode Caps

5

C

F

W

140
052
060

Two green/yellow
wires connected
to the Power
Terminal Block rail

Green/yellow wire
to CM Cap Board
is connected to
ground

Solid Ground
1. CM Cap jumper wire should be connected

to ground with a metal screw. Verify. If
necessary, remove the nylon screw/spacer
and insert a metal M5 x 8 screw. Torque to
3.2 N•m (28 lb•in).

2. MOV/Input Filter Cap jumper wires should

be connected to ground with a metal screw.
Verify. If necessary, remove the nylon screw/
spacer and insert a metal M5 x 12 screw.

Non-Solid Ground
1. CM Cap jumper wire should be insulated

from ground with a nylon screw/spacer.
Verify. If necessary, remove the metal screw
and insert a M5 x 15 nylon screw/spacer.

2. MOV/Input Filter Cap jumper wires should

be insulated from ground with a nylon
screw/spacer. Verify. If necessary, remove
the metal screw and insert a
M5 x 20 nylon screw/spacer.

E
F
T

W

077
082
099
098

Two green/yellow
wires connected
to chassis ground

Green/yellow wire
to CM Cap Board
is connected to
ground

Solid Ground
1. CM Cap jumper wire should be connected

to ground with a metal screw. Verify. If
necessary, remove the nylon screw/spacer
and insert a metal M5 x 8 screw. Torque to
3.2 N•m (28 lb•in).

2. MOV jumper wire should be connected to

ground with metal screws. Verify. If
necessary, remove the nylon screw/spacers
and insert a metal M5 x 12 screws.

3. Input Filter Cap jumper wire should be

connected to ground with a metal screw.
Verify. If necessary, remove the nylon screw/
spacer and insert metal M5 x 8 screw.

Non-Solid Ground
1. CM Cap jumper wire should be insulated

from ground with a nylon screw/spacer.
Verify. If necessary, remove the metal screw
and insert a M5 x 15 nylon screw/spacer.

2. MOV jumper wire should be insulated from

ground with a nylon screw/spacer. Verify. If
necessary, remove the metal screws and
insert a M5 x 20 nylon screw/spacer.

3. Input Filter Cap jumper wire should be

insulated from ground with a nylon screw/
spacer. Verify. If necessary, remove the
metal screws and insert a M5 x 15 nylon
screw/spacer.

Frame 5 continued on next page

(1)

AC input drives only. MOV’s and input filter caps do not exist on DC input drives.

(2)

When removing MOV’s, the input filter capacitor must also be removed.

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

CM Cap

MOV

MOV / Input Filter Cap

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75 C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

PE

CM Cap

MOV

MOV

Input Filter

Cap