Advanced group parameters, English-10 – Rockwell Automation 22A PowerFlex 4 Quick Start FRN 6.xx User Manual

Page 12

Advertising
background image

English-10

Advanced Group Parameters

No. Parameter

Min/Max

Display/Options

Default

A051

A052

[Digital In1 Sel]

I/O Terminal 05

[Digital In2 Sel]

I/O Terminal 06

0/26

0 = “Not Used”

1 = “Acc 2 & Dec 2”

2 = “Jog”

3 = “Aux Fault”

4 = “Preset Freq”

5 = “Local”

6 = “Comm Port”

7 = “Clear Fault”

8 = “RampStop,CF”

9 = “CoastStop,CF”

10 = “DCInjStop,CF”

11 = “Jog Forward”

12 = “Jog Reverse”

13 = “10V In Ctrl”

14 = “20mA In Ctrl”

26 = “Anlg Invert”

4

A055 [Relay Out Sel]

0/21

0 = “Ready/Fault”

1 = “At Frequency”

2 = “MotorRunning”

3 = “Reverse”

4 = “Motor Overld”

5 = “Ramp Reg”

6 = “Above Freq”

7 = “Above Cur”

8 = “Above DCVolt”

9 = “Retries Exst”

10 = “Above Anlg V”

20 = “ParamControl”

21 = “NonRec Fault”

0

A056 [Relay Out Level]

0.0/9999

0.1

0.0

A067 [Accel Time 2]

0.0/600.0 Secs

0.1 Secs

20.0 Secs

A068 [Decel Time 2]

0.1/600.0 Secs

0.1 Secs

20.0 Secs

A069 [Internal Freq]

0.0/240.0 Hz

0.1 Hz

60.0 Hz

A070

A071

A072

A073

[Preset Freq 0]

(1)

[Preset Freq 1]

[Preset Freq 2]

[Preset Freq 3]

0.0/240.0 Hz

0.1 Hz

0.0 Hz

5.0 Hz

10.0 Hz

20.0 Hz

(1)

To activate [Preset Freq 0] set P038 [Speed Reference] to option 4.

A078 [Jog Frequency]

0.0/[Maximum Freq]

0.1 Hz

10.0 Hz

A079 [Jog Accel/Decel]

0.1/600.0 Secs

0.1 Secs

10.0 Secs

A080 [DC Brake Time]

0.0/90.0 Secs

0.1 Secs

0.0 Secs

A081 [DC Brake Level]

0.0/(Drive Amps

× 1.8) 0.1 Amps

Amps

× 0.05

A082 [DB Resistor Sel]

0/99

0 = Disabled

1 = Normal RA Res

2 = NoProtection

3-99 = % of Duty Cycle

0

A083 [S Curve %]

0/100%

1%

0% (Disabled)

A084 [Start Boost]

1/14

Settings in % of base voltage.

8

7 (5 HP Drives)

Variable Torque

Constant Torque

1 = “30.0, VT”

5 = “0.0, no IR”

10 = “10.0, CT”

2 = “35.0, VT”

6 = “0.0”

11 = “12.5, CT”

3 = “40.0, VT”

7 = “2.5, CT”

12 = “15.0, CT”

4 = “45.0, VT”

8 = “5.0, CT”

13 = “17.5, CT”

9 = “7.5, CT”

14 = “20.0, CT”

A088 [Maximum Voltage]

20/Rated Volts

1 VAC

Rated Volts

A089 [Current Limit]

0/(Drive Amps

× 1.8) 0.1 Amps

Amps

× 1.5

A090 [Motor OL Select]

0/2

0 = “No Derate”

1 = “Min Derate”

2 = “Max Derate”

0

A091 [PWM Frequency]

2.0/16.0 kHz

0.1 kHz

4.0 kHz

A092 [Auto Rstrt Tries]

0/9

1

0

A093 [Auto Rstrt Delay]

0.0/300.0 Secs

0.1 Secs

1.0 Secs

A094 [Start At PowerUp]

0/1

0 = “Disabled”

1 = “Enabled”

0

A095 [Reverse Disable]

0/1

0 = “Rev Enabled”

1 = “Rev Disabled”

0

A096 [Flying Start En]

0/1

0 = “Disabled”

1 = “Enabled”

0

A097 [Compensation]

0/3

0 = “Disabled”

1 = “Electrical”

2 = “Mechanical”

3 = “Both”

1

A098 [SW Current Trip]

0.0/(Drive Amps

× 2) 0.1 Amps

0.0 (Disabled)

A099 [Process Factor]

0.1/999.9

0.1

30.0

A100 [Fault Clear]

0/2

0 = “Ready/Idle”

1 = “Reset Fault”

2 = “Clear Buffer”

0

A101 [Program Lock]

0/1

0 = “Unlocked”

1 = “Locked”

0

A102 [Testpoint Sel]

0/FFFF

1 Hex

400

Input State of Digital In 1

(I/O Terminal 05)

Input State of Digital In 2

(I/O Terminal 06)

Frequency Source

Accel / Decel Parameter Used (2)

0

0

[Preset Freq 0]

[Accel Time 1] / [Decel Time 1]

1

0

[Preset Freq 1]

[Accel Time 1] / [Decel Time 1]

0

1

[Preset Freq 2]

[Accel Time 2] / [Decel Time 2]

1

1

[Preset Freq 3]

[Accel Time 2] / [Decel Time 2]

(2) When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.

See the PowerFlex 4 User Manual for more information on parameters.