Mounting considerations, General grounding requirements, Ce conformity – Rockwell Automation 22A PowerFlex 4 Quick Start FRN 6.xx User Manual

Page 4

Advertising
background image

English-2

• Mount the drive upright on a flat, vertical and level surface.

• Protect the cooling fan by avoiding dust or metallic particles.

• Do not expose to a corrosive atmosphere.

• Protect from moisture and direct sunlight.

Minimum Mounting Clearances

Ambient Operating Temperatures

Refer to the PowerFlex 4 User Manual for details on how to comply with

the Low Voltage (LV) and Electromagnetic Compatibility (EMC)

Directives.

Mounting Considerations

Min. Panel Thickness

Screw Size

Screw Torque

DIN Rail

1.9 mm (0.0747 in.)

M4 (#8-32)

1.56-1.96 N-m (14-17 lb.-in.) 35 mm

Ambient Temperature

Enclosure Rating

Minimum Mounting

Clearances

Minimum

Maximum

-10°C (14°F)

40°C (104°F)

IP 20/Open Type

Use Mounting Option A

IP 30/NEMA 1/UL Type 1

(1)

(1)

Rating requires installation of the PowerFlex 4 IP 30/NEMA 1/UL Type 1 option kit.

Use Mounting Option B

50°C (122°F) IP 20/Open Type

Use Mounting Option B

25 mm

(1.0 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

Mounting Option A

No clearance required between drives.

Mounting Option B

Closest object that

may restrict air flow

through the drive heat

sink and chassis

See page 12 for

mounting dimensions.

General Grounding Requirements

U/T1

V/T2

W/T3

R/L1

S/L2

T/L3

SHLD

Important: The MOV to ground jumper must be

removed if the drive is installed on an ungrounded or

resistive grounded distribution system.
Tighten screw after jumper removal.

Jumper

Location

CE Conformity