Control terminal block, English-5 – Rockwell Automation 22A PowerFlex 4 Quick Start FRN 6.xx User Manual

Page 7

Advertising
background image

English-5

Control Terminal Block

No. Signal

Default

Description

Param.

R1

Relay N.O.

Fault

Normally open contact for output relay.

A055

R2

Relay Common

Common for output relay.

R3

Relay N.C.

Fault

Normally closed contact for output relay.

A055

Sink/Source DIP Switch

Source (SRC)

Inputs can be wired as Sink (SNK) or Source (SRC) via DIP Switch setting.

01

Stop(1)

Coast

The factory installed jumper or a normally closed input

must be present for the drive to start.

P036(1)

02

Start/Run FWD

Not Active

Command comes from the integral keypad by default. To

disable reverse operation, see A095 [Reverse Disable].

P036, P037

03

Direction/Run REV

Not Active

P036, P037,

A095

04

Digital Common

For digital inputs. Electronically isolated with digital inputs

from analog I/O.

05

Digital Input 1

Preset Freq

Program with A051 [Digital In1 Sel].

A051

06

Digital Input 2

Preset Freq

Program with A052 [Digital In2 Sel].

A052

11

+24V DC

Drive supplied power for digital inputs.

Maximum output current is 100mA.

12

+10V DC

Drive supplied power for 0-10V external potentiometer.

Maximum output current is 15mA.

P038

13

0-10V In(3)

Not Active

For external 0-10V input supply

(input impedance = 100k ohm) or potentiometer wiper.

P038

14

Analog Common

For 0-10V In or 4-20mA In. Electronically isolated with

analog inputs from digital I/O.

15

4-20mA In(3)

Not Active

For external 4-20mA input supply

(input impedance = 250 ohm).

P038

16

RS485 (DSI) Shield

Terminal should be connected to safety ground - PE when

using the RS485 (DSI) communications port.

(3) Only one analog frequency source may be connected at a time. If more than one reference is connected at the same

time, an undetermined frequency reference will result.

01
02
03
04
05
06

11
12

13
14
15
16

Stop

(1)

Start/Run FWD

(2)

Direction/Run REV
Digital Common
Digital Input 1
Digital Input 2

R1
R2
R3

Relay N.O.

Relay Common

Relay N.C.

+24V DC
+10V DC
0-10V In
Analog Common
4-20mA In
RS485 Shield

+24V

+10V

SRC

SNK

Typical

SNK Wiring

Typical

SRC Wiring

1

8

RS485

(DSI)

R1 R2 R3

01 02 03 04 05 06

11 12 13 14 15 16

SNK

SRC

(1)

Potentiometer

must be

1-10k ohm

2 Watt Min.

30V DC 125V AC 240V AC

Resistive

3.0A

3.0A

3.0A

Inductive

0.5A

0.5A

0.5A

(1)

Important: I/O Terminal 01 is

always a coast to stop input except

when P036 [Start Source] is set to

“3-Wire” control. In three wire

control, I/O Terminal 01 is controlled

by P037 [Stop Mode]. All other stop

sources are controlled by P037

[Stop Mode].

Important: The drive is shipped with

a jumper installed between I/O

Terminals 01 and 11. Remove this

jumper when using I/O Terminal 01

as a stop or enable input.

(2)

Two wire control shown. For

three wire control use a momentary

input

on I/O Terminal 02 to

command a start. Use a maintained

input

for I/O Terminal 03 to

change direction.

Refer to the PowerFlex 4

User Manual for more

information.

P036

[Start Source]

Stop

I/O Terminal 01

Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

2-Wire

Per P037

Coast

RS485 Port

Per P037

Coast