Minimum mounting clearances, Ambient operating temperatures, Minimum mounting clearances -2 – Rockwell Automation 20T PowerFlex Diode Bus Supply User Manual

Page 14: Ambient operating temperatures -2

Advertising
background image

1-2

Installation/Wiring

PowerFlex Diode Bus Supply User Manual
Publication 20T-UM001D-EN-P

Minimum Mounting
Clearances

Ambient Operating Temperatures

The Diode Bus Supply is designed to operate at 0…40 °C (32…104 °F)
ambient without derating. Remove the label from the top to operate the
Diode Bus Supply in ambients 41 °C up to 50 °C (104 °F up to 122 °F).

Important: Removing the adhesive label changes the enclosure rating from

NEMA Type 1 Enclosed to Open Type. This also changes the
side-to-side mounting clearance requirement.

Ensure that proper cooling is provided to the Diode Bus Supply to stay
under the 40 °C rated specification. Add exhaust fans to the front or top of
the enclosure bay and provide a filtered opening at the bottom of the cabinet
bay.

The Diode Bus Supply watt loss (from specification section) is 500 W at
120 A. The three-phase AC line reactor watt losses are listed in the 1321
Power Conditioning Products Technical Data, publication

1321-TD001

.

It is recommended that the system integrator completes a thermal evaluation
to ensure adequate cooling to maintain proper operating conditions for each
cabinet or bay.

100 (4)

100 (4)

100 (4)

100 (4)

50 (2)

50 (2)

No Adhesive Label on Top

With Adhesive Label on Top

Dimensions are in millimeters and (inches).

See

Appendix A

for detailed dimension information.