Maximum Loading

To avoid overloading the Diode Bus Supply, the following requirement
applies:

The DC Input current sum (Normal Duty or Heavy Duty rating at 40 °C/
104 °F) of the connected drive(s) must not exceed the Bus Supply
continuous DC Bus output current rating of 120 amps at 40 °C/104 °F.

For the DC Input Current values of the drives, see tables in the respective
drive documentation.

Table 1.A

and

Table 1.B

provide guidance on the nominal operation of the

Diode Bus Supply. No overload capability is built into the tables.

When an overload is being utilized in connected drives or products, that
overload current must be accounted for in the calculation to properly size
the Diode Bus Supply.

Table 1.A Normal Duty ND

Table 1.B Heavy Duty HD

AC Input Fusing

The Diode Bus Supply can be installed with delay type AC input line fuses.
National and local industrial safety regulations and/or electrical codes may
determine additional requirements for these installations.

TIP: When paralleling two Diode Bus Supplies, see

Paralleling Diode Bus

Supplies on page 1-11

for details.

Drive Rating

Drive DC Input Current

Diode Bus Supply

(1)

(1)

No overload capability.

DC
Voltage

ND
Power

ND DC Input
Currents

ND DC Input
Current Sum

Maximum DC
Output Amps

AC Input
Voltage

540V

30 + 22 = 52 kW

61.9 + 47.5

109.4 A

120 A

400V

650V

2 x 40 = 80 Hp

2 x 55.7

111.4 A

120 A

480V

Drive Rating

Drive DC Input Current

Diode Bus Supply

(1)

(1)

No overload capability.

DC
Voltage

HD
Power

HD DC Input
Currents

HD DC Input
Current Sum

Maximum DC
Output Amps

AC Input
Voltage

540V

37 + 2 x 1.5 = 40 kW

95.1 + 2 x 5.3

105.7 A

120 A

400V

!

ATTENTION: The PowerFlex Diode Bus Supply does not
provide branch short circuit protection. Specifications for the
recommended fusing to provide protection against short circuits
are provided in

Table A.A on page A-4

.