Ac input fusing, Fuse types – Rockwell Automation 20T PowerFlex Diode Bus Supply User Manual

Page 34

Advertising
background image

A-4

Supplemental Information

PowerFlex Diode Bus Supply User Manual
Publication 20T-UM001D-EN-P

AC Input Fusing

Table A.A

below provides output ampere ratings for the Diode Bus Supply

(including continuous, 1 minute, and 3 seconds) and recommended AC line
input fusing information. The short circuit protection fuses are acceptable
for UL and IEC requirements. Sizes listed are recommended sizes based on
40 °C (104 °F) and the U.S. NEC. Other country, state or local codes may
require different ratings.

Fuse Types

Refer to the recommended types listed below.

• IEC – BS88 (British Standard) Parts 1 & 2

(1)

, EN60269-1,

Parts 1 & 2, type gG or equivalent should be used.

• UL – UL Class RK1 or J must be used.

(2)

Table A.A AC Input Current Ratings and Recommended Input Fusing

(1)

Typical designations include, but may not be limited to, the following; Parts 1 & 2:
AC, AD, BC, BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, and GH.

(2)

For 600V, (Ferraz Shawmut) Class J: AJT150 (with open fuse indicator),

Class RK1: A6D150R

(Bussman)

Class J: LPJ-150SP,
Class RK1: LPS-RK-150SP or equivalent

Bus Supply
Catalog
Number

Input Ratings Output Amps

Dual Element
Time Delay Fuse

Amps

kVA

Cont.

1 Min. 3 Sec. Amps

240 Volt / 60 Hz AC Input

125
IEC - gG
or
150
UL - Class RK1 or J

20TD120

105

44

120

180

240

400 Volt / 50 Hz AC Input

20TD120

105

73

120

180

240

480 Volt / 60 Hz AC Input

20TD120

105

87

120

180

240

500 Volt / 50 Hz AC Input

20TE120

105

91

120

180

240

600 Volt / 60 Hz AC Input

20TE120

105

109

120

180

240

Advertising