Start Up/Troubleshooting

2-3

PowerFlex Diode Bus Supply User Manual

Publication 20T-UM001D-EN-P

Power On LED

The green Power On LED is visible through the front panel and will
illuminated if power is applied.

Figure 2.1

Power On LED

Troubleshooting

Table 2.A Possible Faults and Corrective Actions

!

ATTENTION: The Power On LED is only operational when the
unit is energized. Servicing energized equipment can be
hazardous. Severe injury or death can result from electrical shock,
burn, or unintended actuation of the controlled equipment. Follow
safety-related practices of NFPA 70E, Electrical Safety For
Employee Workplaces. DO NOT work alone on energized
equipment!

Power On LED

Fault

Cause

Corrective Action

Heat sink
Overtemperature

Heat sink temperature
exceeds maximum
rating

1. Verify that maximum ambient temperature has not

been exceeded.

2. Check Overtemperature Switch (N.C. contacts) at

control terminals 10 and 11.

3. Check fan for correct operation.

4. Check for excess load on the Diode Bus Supply.

5. Check for minimum mounting clearance around the

Diode Bus Supply.

6. Contact your local Rockwell Automation sales office.

DC Output
Voltage Loss

Loss of DC Bus power
and loss of 24V power

1. Check 3-phase AC incoming power for undervoltage

or phase loss.

2. Check Diode Bus Supply input circuit breaker or fuses.

3. Contact your local Rockwell Automation sales office.

Loss of 24V power
only (used for fan
power only)

1. Check fans for correct operation.

2. Check Overtemperature switches.

3. Contact your local Rockwell Automation sales office.