Paralleling diode bus supplies, Paralleling diode bus supplies -11, O diode bus supplies, see – Rockwell Automation 20T PowerFlex Diode Bus Supply User Manual

Page 23: Paralleling diode bus, For details, Figure 1.6

Advertising
background image

Installation/Wiring

1-11

PowerFlex Diode Bus Supply User Manual

Publication 20T-UM001D-EN-P

Figure 1.6

Removing the Phase-to-Ground Jumpers for the MOV, Input FIlter, and
Common Mode Capacitors

Paralleling Diode Bus
Supplies

Up to two Diode Bus Supplies can be paralleled for operation. To parallel
Diode Bus Supplies, an AC line reactor must be used at the input of each
Bus Supply (see

Figure 1.7

). One-percent reactors (catalog number

1321-3R130-A) can be used, unless 3% reactors (catalog number
1321-3R130-B) are required based on the maximum transformer size listed
in

Line Reactors on page A-5

.

When paralleling Diode Bus Supplies, follow these guidelines:

• A maximum of (2) two Diode Bus Supplies can be paralleled.

• Each Diode Bus Supply must be derated by 3%. This results in a DC Bus

continuous output current rating of 233 Amps (0.97 x 2 x 120).

• It is recommended to use AC line fuses with an open fuse indicator. See

AC Input Fusing on page A-4

for details on recommended fusing.

Important: It is recommended to keep all wired connections identical in

size and length. This includes the AC line connection to the
three-phase AC line reactors and from the three-phase AC line
reactors to the Diode Bus Supply.

MOVs

Ground Jumper

To Diode Bridge
Rectifier Unit

To

+DC, -DC

MOV

TB1

R / L1

S / L2

T / L3

PE

GND

12

J3

J2

J4

7

4

1

4

1

Power Supply

Board DFPS

Common Mode
Capacitors

Input Filter

Capacitors

Input Filter and

Common Mode Capacitors

Ground Jumper

Advertising