Control Wiring

Important points to remember about control wiring:

• Use Copper wire only. Wire gauge requirements and recommendations

are based on 75 °C (168 °F). Do not reduce wire gauge when using
higher temperature wire.

• Wire with an insulation rating of 600V or greater is recommended.

• Control wires outside the cabinet

should be separated from power wires

by at least 0.3 meters (1 foot).

Drive Run Interlock

To protect the Diode Bus Supply from overtemperature, the normally closed
contacts (Bus Supply Overtemperature - terminals 10 and 11) should be
wired to either the AC line input contactor for the Diode Bus Supply or the
Run interlock circuit (enable input) of each connected drive. This ensures
that the drives are stopped in case of Bus Supply Overtemperature.

PE

8

9

11

10

DC +

DC -

R (L1) S (L2) T (L3)

GND

12

MOV

Terminal

Description

Notes

Power Connections

DC +

DC Bus (+)

DC Bus Connection (+)

DC -

DC Bus (-)

DC Bus Connection (–)

PE

PE Ground

Safety Ground

R

R (L1)

AC Line Input Power

S

S (L2)

AC Line Input Power

T

T (L3)

AC Line Input Power

Control Connections

8

24V Fan Supply

Internal connection to extend fan supply leads
(must be disconnected in case of fan replacement)

9

10

NC Contact Output
(F1, F2)

Opens with power stack overtemperature.
(See

Appendix A

for contact ratings.)

11

12

Jumper
MOVs to Ground

Disconnect MOV neutral point and ground by removing this
jumper. (See

page 1-10

for details.)