Step 1: removing power from the drive – Rockwell Automation 20D DriveLogix Controller for PowerFlex 700S Phase I Drives User Manual

Page 3

Advertising
background image

DriveLogix Controller for PowerFlex 700S Phase I Drives

3

Step 1: Removing Power
from the Drive

1. Turn off and lock out input power. Wait five minutes.

2. Verify that there is no voltage at the drive’s input power terminals.

3. Measure the DC bus voltage at the DC+ & DC- terminals on the Power

Terminal Block. The voltage must be zero.

!

ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing
any work on the drive. Measure the DC bus voltage at the +DC &
–DC terminals of the Power Terminal Block. The voltage must
be zero.

Remove power before making or breaking cable connections.
When you remove or insert a cable connector with power
applied, an electrical arc may occur. An electrical arc can cause
personal injury or property damage by:

sending an erroneous signal to your system’s field devices,
causing unintended machine motion

causing an explosion in a hazardous environment

Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.

L1

L2

L3

O

I

Advertising