Diagnostic, External faults, Internal faults – Rockwell Automation 440R MSR42 Control Module User Manual User Manual

Page 12: Original instructions

Advertising
background image

10

Light Curtain Multi-Function Control Module User Manual

Original instructions

Following connections may be used for test inputs.

Figure 12: Connection possibilities for the input

The timing of test input is as follows (Figure 13):

Table 12: Timing during testing

Figure 13: Test timing diagram (minimum off time = see configuration control document)

t

R

means the max response time of the total system (see page 4). The

machine controller has to check the output of the OSSD during such a
test. If the machine controller detects an error, then the machine
controller should not allow the machine to restart, respectively must stop
the machine immediately.

In case of a test failure the status output “Info2” will also provide a failure
signal.

Table 13

Diagnostic

In the event of a fault condition, it will be indicated by

1. the red LED of a connected GuardShield Micro 400 safety light

curtain are blinking

2. can be visually noticed in that the blue OptiLink LED (located on the

side of a MSR42 unit) is off

3. one of the info outputs (if configured)

In this situation both safety outputs are low and the relays of the
extension modules are open, and the controller unit is now in the so-
called lock-out mode.

Two options exist to leave the lock-out mode:

• Power up. If the fault is still present the controller will again show

the lock-out mode.

• A start impulse longer than 10 s acts like a power up.

More detailed lock out information can be obtained with help of the
USB/optical interface (445L-AF6150) and the software “Configuration
& Diagnostic Tool”.

External faults

The following external faults apply to the “Out of Box” configurations
only. Reference Table 14 for detailed information.

Table 14

Programmed Configuration Diagnostics can be obtained with the use of
USB / Optical Interface (445l-AF6150) and the software
“Configuration and Diagnostic Tool”

Internal faults

The following internal faults apply to the “Out of Box” configurations
only. Reference Table 15 for detailed information.

Table 15

The lock-out mode of a MSR42 control module may be reset by one of
two methods:

1. Power down, then Power up. If the fault is still present the module

will again lock-out.

2. A start signal longer than 10 seconds acts like a power up.

Further diagnosis possibilities are possible with the software
Configuration & Diagnostic Tool in combination with the USB/optical
interface. If the MSR42 unit has a lock-out, the exact fault description
can be determined with these tools. An exact description is available at
any time after a lock-out, as long as the MSR42 unit is still in the lock-out
condition.

Time

Value in ms

Response time to test signal

t

1

≤ t

R

ime to test

t

2

≤ t

1

Restart time after test

t

3

≥ t

R

Terminal

LED green

LED red

IN 1 or IN 2

External test signal high

External test signal low (test running)

short circuited

Test input

OSSD 1 / OSSD 2

open

t

1

t

2

t

3

No

Fault profile

Fault description

Measures & instructions

1

No power LED

No Power Connection to +24
VDC OV

Check power connections and
power supply

2

Light curtain LED(s) are
flashing red

Light curtain Rx / Tx are swapped

Reverse Rx / Tx connections and
retry

Open / missing light curtain
cable

Replace expansion cable on the
light curtain that is not flashing

Defect in light curtain

Replace light curtain

3

OSSD1 & OSSD2 LEDs are
red
No relay outputs

Missing reset switch for manual
reset

Add rest switch with N/O contact

Missing 24 VDC to GPIO3 and
GPIO4 for automate reset.

Add 24VDC jumper to GPIO3 and
GPIO4

Missing 24VDC to IN1 and IN2

Add 24VDC jumper to IN1 and
IN2

No start release signal from
external contactors

Check wiring and function of
external contacts

No

Fault profile

Fault description

Measures & instructions

1

No Power LED

Power supply is ok but MSR42
relay does not power up

Replace the MSR42 and retry

2

Relay is in Lockout mode
Will not initialize

All input and reset LEDS are ok.
No external faults were
detected. Relay locks upon
power up and will not release

Replace the MSR42 and retry