MSR42 Control Module User Manual

Original instructions

Appendix

Special MSR42 control module features -- for existing customers.

Interrupt Ignore Time

This function is not included in the standard version.

A limited time a light curtain interruption will be ignored. This may be
used when parts move through the light curtain at high speed and the
safety output should not switch, but yet a person moving through the
light curtain should be detected and cause the safety output to switch off.

Activating this operating mode, a limited time a light curtain
interruption will be ignored. This may be used when parts may move at a
fast speed through the light curtain without interrupting, but a human
will interrupt the light curtain at time longer than the configurated time.

The Interrupt Ignore Time function has to be activated by the MSR42
“Configuration & Diagnostic Tool” software and downloaded to the
MSR42 control module with help of the USB/optical interface (445L-
AF6150)

Start pulse duration
Min.
Max.

50 ms
5s See page 7

Test pulse duration (min.)

response time x 2

Control current into:
GPIO1 – GPIO4

7 mA each at U

N

(coded)

Maximum cable length for safety switches

50 m out and back (total 100 m) See page 6 or 10

Safety Prevention Lamp
Minimum current at Lamp

0.9 A with lamp switched on

GPIO1 – GPIO4 Outputs to safety components

Nominal voltage

U

N

– 2 V (coded)

(Short circuit protected)

Current max

100 mA (short-circuit protected)

Leakage current

I

MAX Off

= 0.05 mA (C

LOAD

= 100 μF)

Info 1, Info 2 Status Outputs (PNP)

Voltage

U

N

– 2 V

Current max

100 mA (short-circuit protected)

Leakage current

I

MAX Off

= 0.05 mA (C

LOAD

= 4.7 μF)

2 OSSD semi conductor outputs (PNP)

Voltage

U

N

- 2 V

Current Max

400 mA
short-circuit protected and with cross-fault
detection

Leakage current

I

MAX Off

= 0.1 mA (C

LOAD

= 3.3 μF)

Max. response time t(C) with UN protective mode
See page 4

≤ 15 ms

Max. response time t(GPIO) with UN protective
mode See page 4

≤ 130 ms

Minimal off time

82 ms

Safety Related Parameter

Probability of a dangerous failure per hour PFH

D

6.0 E-9 1/h
MSR42 & MSR45E & Micro 400

9.0 E-10 1/h
MSR42 & MSR41 Control Module

3.0 E-10 1/h
MSR45E Expander Module

4.0 E-9 1/h
Micro 400 Light Curtain

Performance Level PL

PL e, Cat. 4 (EN ISO 13849-1)

Safety Integrity Level

SIL CL 3 (IEC 61508 / IEC 62061)

Inputs

Interrupt Ignore Time will increase the
response time. The response time is given
in the corresponding configuration
control document. Recalculate the safety
distance.