Safety components, Safety override, Original instructions – Rockwell Automation 440R MSR42 Control Module User Manual User Manual
Page 9
 
7
MSR42 Control Module User Manual
Original instructions
Recommended surge suppressors are:
Table 6
Safety Components
The connected safety components (e.g. safety switches, position switch, 
emergency stop buttons, cable pull safety switches) must satisfy the 
relevant standards for application within safety areas:
• Emergency stop button : EN 418
• Safety switch : EN 60947-5-1
• Light curtains : EN 61496-1 / -2
• etc.
as well as the requirements of the safety analysis. It is essential that the 
components contain 2 force guided, normally closed (NC) contacts 
(Figure 8), and that they are approved for the relevant safety level or 
category.
As a basic rule to increase reliability, it is recommended to use safety 
components with integrated gold contacts. Safety components, can be 
connected to “GPIO1” through “GPIO4” as shown below. The inputs 
are short-circuit and cross fault monitored.
Figure 8: Connecting an emergency stop
In general the two circuits of dual channel safety components are cross-
fault monitored. A short of these two circuits would lead to an 
emergency stop of the MSR42 control module. The two circuits are also 
time monitored. This means, if one circuit changes e.g. of an emergency 
stop, the second circuit has to follow within 5 seconds. If this is not the 
case, the MSR42 interprets this as a fault and the controller switches off 
the safety circuit.
Depending on the configuration and the application, there may be more 
terminals than components needed. The unused ports may be bridged. 
Shielded cables are recommended for bridging to reduce the input of 
EMC.
Table 7
Safety Override
In Figure 9 a “Safety Override” key switch and a safety prevention lamp is 
shown. With the “Safety Override” key switch it is possible to override 
the safety function of the Micro400 light curtain. This means that if the 
override key switch is activated, the safety outputs stay high even if e.g. 
the protective field is interrupted. 
Figure 9: Connecting a Safety Override key switch and the associated lamp
Depending on the risk evaluation when using a “Safety override” key 
operated switch a corresponding indicator lamp must also be connected. 
The connection for this safety override lamp can be configured to be 
current controlled (see Technical Data chapter 14). This means, the 
current (I) of the individual lamp must remain between (Imin < I < 
Imax). If the monitored current is not within these limits, the light 
curtain will not be overridden although the safety override key switch is 
activated.
The safety override lamp used has to fulfil the requirements of EN 61496 
and has to be mounted close to the protective field and be clearly visible 
to the machine operator. Safety override only takes place when both 
circuits are closed. Likewise safety override only takes place when both 
circuits were opened before becoming closed. A cross-fault will be 
1. In cases where the MSR42 control
module is installed without expander 
modules the function external device 
monitoring (EDM) or start release 
must always be used, the only 
exceptions are if the PNP outputs are 
connected with another safety relay 
or a safety PLC.
2. Through the use of start release or
EDM, it is possible to switch external 
“power” contactors within the safety 
circuit. Such contactors often deal 
with large inductive loads, which 
during the switching off phase can 
create large potential peaks. For this 
reason surge suppressors are highly 
recommended. Surge suppressors 
must be connected parallel to the 
external contactors (e.g. Figure 4). 
They may never be connected parallel 
to the contacts of a MSR45E expander 
module. Surge suppressors may 
drastically increase the off delay time 
of the contactors. Diodes are not 
allowed to be used as surge 
suppressors, for exactly this reason.
Supply voltage [V]
Resistor R [
Ω]
Condenser C [μF]
24
100
2.2
115 - 230
220
0.2
Terminal
LED green
LED off
GPIO3
Contact GPIO1/GPIO3 closed
Contact GPIO1/GPIO3 open
GPIO4
Contact GPIO2/GPIO4 closed
Contact GPIO2/GPIO4 open