Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual
Page 134

134
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Appendix C
EtherNet/IP Objects
5
Get
Data Type
USINT
0xC2 = SINT (8-bits)
0xC3 = INT (16-bits)
0xC4 = DINT (32-bits)
0xC6 = USINT (8-bits)
0xC7 = UINT (16-bits)
0xCA = REAL (32-bits)
0xD2 = WORD (16-bits)
6
Get
Data Size
USINT
(3)
7
Get
Parameter Name String
SHORT_STRING
(3)
8
Get
Units String
SHORT_STRING
(3)
9
Get
Help String
SHORT_STRING
(3)
10
Get
Minimum Value
(1)
(3)
11
Get
Maximum Value
(1)
(3)
12
Get
Default Value
(1)
(3)
13
Get
Scaling Multiplier
UINT
(3)
14
Get
Scaling Divisor
UINT
(3)
15
Get
Scaling Base
UINT
(3)
16
Get
Scaling Offset
UINT
(3)
17
Get
Multiplier Link
UINT
(3)
18
Get
Divisor Link
UINT
(3)
19
Get
Base Link
UINT
(3)
20
Get
Offset Link
UINT
(3)
21
Get
Decimal Precision
USINT
(3)
(1) Access rule is defined in bit 4 of instance attribute 4. 0 = Get/Set, 1 = Get.
(2) Specified in descriptor, data type, and data size.
(3) Value varies based on parameter instance.
(4) Refer to the CIP Common specification for a description of the link path.
Attribute ID
Access Rule
Name
Data Type
Description