Commissioning the adapter – Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual
Page 21

Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
21
Setting Up the Adapter
Chapter 2
For more information on how to set different combinations of the control and
Reference functions, see the PowerFlex 525 drive user manual,
publicatio
.
Commissioning the Adapter
To commission the embedded EtherNet/IP adapter, you must set a unique IP
address. See the
for details about IP addresses. Use either a BOOTP
server or parameters to set the IP address after connecting the adapter to the
network and applying power to the drive.
By default, the adapter is configured to accept an IP address from a BOOTP
server. For details, see
. To set the IP address using
parameters, see
Setting the IP Address, Subnet Mask, and Gateway Address on
IMPORTANT
New settings for some parameters (for example, parameters C129 [EN IP
Addr Cfg 1] through C132 [EN IP Addr Cfg 4]) are recognized only when
power is applied to the adapter. After you change parameter settings, cycle
drive power.