Message structure for execute_dh – Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual
Page 136

136
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Appendix C
EtherNet/IP Objects
Message Structure for Execute_DH+
The embedded EtherNet/IP adapter supports the following PCCC command
types:
For more information regarding PCCC commands, see DFI Protocol and
Command Set Manual (Allen-Bradley publication
).
Request
Response
Name
Data Type
Description
Name
Data Type
Description
DLink
UINT
Destination Link ID
DLink
UINT
Destination Link ID
DSta
USINT
Destination Station number
DSta
USINT
Destination Station number
DUser
USINT
Destination “User” number
DUser
USINT
Destination “User” number
SLink
UINT
Source Link ID
SLink
UINT
Source Link ID
SSta
USINT
Source Station number
SSta
USINT
Source Station number
SUser
USINT
Source User number
SUser
USINT
Source User number
CMD
USINT
Command byte
CMD
USINT
Command byte
STS
USINT
0
STS
USINT
Status byte
TNSW
UINT
Transport word
TNSW
UINT
Transport word. Same value as the request.
FNC
USINT
Function code. Not used for all CMDs.
EXT_STS
USINT
Extended Status. Not used for all CMDs.
PCCC_params
Array of USINT
CMD/FNC specific parameters
PCCC_results
Array of USINT
CMD/FNC specific result data
CMD
FNC
Description
0x06
0x03
Identify host and some status
0x0F
0x95
Encapsulate the other protocol
0x0F
0x00
Word range read
0x0F
0x01
Word range write
N-File
Description
N41
For Single-Drive Mode Only
This N-file lets you read and write control I/O messages. You can write control I/O messages only when
all of the following conditions are true:
• The adapter is not receiving I/O from a scanner. For example, there is no scanner on the network,
the scanner is in idle (program) mode, the scanner is faulted, or the adapter is not mapped to the
scanner.
• The value of N42:3 is set to a non-zero value.
Write
Read
N41:0
N41:1
N42:2
Logic Command Word
Unused
Reference
Logic Status Word
Unused
Feedback
N42
This N-file lets you read and write some values configuring the port
N42:3
Time-out (read/write): Time (in seconds) allowed between messages to the N41 or N44 file. If the
adapter does not receive a message in the specified time, it performs the fault action configured in
parameter C143 [EN Comm Flt Actn].
N42:7
Adapter Port Number (read only): DPI port on the drive to which the adapter is connected.
42:8
Peer Adapters (read only): Bit field of devices having DPI Peer capabilities.