Rockwell Automation 20G PowerFlex 750-Series EMC Plate and Cores - Frames 1…7 User Manual

Page 3

Advertising
background image

Rockwell Automation Publication 750-IN006G-MU-P - February 2014

3

PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7

2…5

All

Step

Frame Procedure

4

continued

1.8 N•m (16 lb•in)
x 2 (Frame 2)

x 3 (Frames 3…5)

T20

#1

Frame 2 Shown

Environments with Vibration
Support Plate is recommended to
provide core support

5

Drain

Shield

Braid

Ground (PE)

5.6 N•m (50 lb•in)

Clamp

#2

M10

Drain wires must be pulled back and
wrapped in a 360 degree pattern over
the shield/braid surface. Do Not fold
the shield back.

Advertising
This manual is related to the following products: