PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
2…5
All
Step
Frame Procedure
4
continued
1.8 N•m (16 lb•in)
x 2 (Frame 2)
x 3 (Frames 3…5)
T20
#1
Frame 2 Shown
Environments with Vibration
Support Plate is recommended to
provide core support
5
Drain
Shield
Braid
Ground (PE)
5.6 N•m (50 lb•in)
Clamp
#2
M10
Drain wires must be pulled back and
wrapped in a 360 degree pattern over
the shield/braid surface. Do Not fold
the shield back.