PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7

5

6

IP00

Step

Frame Procedure

6

continued

IP20,

NEMA/UL Type 0

Flange Mount

to PE Stud

to PE Stud

Input Power (R, S, T)

Shielded or Unshielded

Motor Cable (U, V, W)

Shielded

I/O Signal Shields

I/O Signal Wires

M6 (10 mm) 5.6 N•m (50 lb•in)

PE

The motor cable ground wire connects to the motor PE stud in the drive, however it should

not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width

Modulated (PWM) AC Drives, publication

DRIVES-IN001

for further information.

T20

2.6 N•m (23.0 lb•in)

#1

x6

x6

x4

x6

Input Power (R, S, T)

Shielded or Unshielded

Motor Cable (U, V, W)

Shielded

The cable shield and drain wires must be

terminated at the shield clamp on the conduit

plate. The ground wire must be connected to

the PE stud in the drive; however, it should not

pass through the core.

For use on Frame 6 IP00 drives. After installation,

the drive achieves an IP20 rating.