Rockwell Automation 20G PowerFlex 750-Series EMC Plate and Cores - Frames 1…7 User Manual

Page 4

Advertising
background image

4

Rockwell Automation Publication 750-IN006G-MU-P - February 2014

PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7

1

2…3

4…5

Step

Frame Procedure

6

Input Power (R, S, T)

Shielded or Unshielded

to PE Stud

to PE Stud

Motor Cable (U, V, W)

Shielded

1 Loop

(each wire)

T20 or F - 6.4 mm (0.25 in.)

1.8 N•m (16 lb•in)

PE

I/O Shields

IP20,

NEMA/UL Type 0

Flange Mount

Input Power (R, S, T)

Shielded or Unshielded

Motor Cable (U, V, W)

Shielded

to PE Stud

to PE Stud

I/O Signal Shields

I/O Signal Wires

M4 (7 mm) 1.8 N•m (16 lb•in)

PE

Frame 2 Shown

IP20,

NEMA/UL Type 0

Flange Mount

to PE Stud

to PE Stud

Input Power (R, S, T)

Shielded or Unshielded

Motor Cable (U, V, W)

Shielded

M6 (10 mm) 5.6 N•m (50 lb•in)

PE

I/O Signal Shields

I/O Signal Wires

The motor cable ground wire connects to the motor PE stud in the drive, however it should

not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width

Modulated (PWM) AC Drives, publication

DRIVES-IN001

for further information.

Frame 5 Shown

Advertising