Rockwell Automation Publication 750-IN006G-MU-P - February 2014

5

PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7

600…690V AC Input Drives – Frames 3…7

Step

Frame Procedure

3…5

All

3…4

4

1.8 N•m (16 lb•in)

x 2 (Frame 3)
x 3 (Frames 4…5)

T20

#1

Environments with Vibration
Support Plate is recommended to
provide core support

5

Drain

Shield

Braid

Ground (PE)

5.6 N•m (50 lb•in)

Clamp

#2

M10

Drain wires must be pulled back and
wrapped in a 360 degree pattern over
the shield/braid surface. Do Not fold
the shield back.

6

IP20,

NEMA/UL Type 0

Flange Mount

to PE Stud

to PE Stud

Input Power (R, S, T)

Shielded or Unshielded

Motor Cable (U, V, W)

Shielded

I/O Signal Shields

I/O Signal Wires

M6 (10 mm) 5.6 N•m (50 lb•in)

PE

The motor cable ground wire connects to the motor PE stud in the drive, however it should

not go through the core. Refer to Wiring and Grounding Guidelines for Pulse Width

Modulated (PWM) AC Drives, publication

DRIVES-IN001

for further information.

Frame 4 Shown