PowerFlex 750-Series EMC Plate and Core(s) – Frames 1…7
7
IP54
6…7
Step
Frame Procedure
6
continued
Input Power (R, S, T)
Shielded or Unshielded
Motor Cable (U, V, W)
Shielded
x4
x2
x6
T30
5.2 N•m (46.0 lb•in)
#1
The cable shield and drain wires must be
terminated at the shield clamp on the conduit
plate. The ground wire must be connected to
the PE stud in the drive; however, it should not
pass through the core.
Cabinet not shown
Adheres to
cabinet
7
Frame 6
Frame 7