Setting the devicenet‰ node address, Start rsnetworx and select tools from the menu bar, Setting the devicenet – Rockwell Automation 800F DeviceNet Pendant Stations User Manual
Page 28: Node address
Advertising

3–2
Installation and Mounting
Publication 800-UM001A-EN-P – June 2004
Setting the DeviceNet
™ Node Address
The Node Address for the 800E/F Pendant Stations must be set
through Node Commissioning. The factory default is Node 63.
To set the DeviceNet
™ Node Address:
1. Start RSNetWorx and select TOOLS from the Menu Bar.
2. Select Node Commissioning. The following screen will appear.
3. Select Browse and select the Pendant Station at Node 63.
4. Change the Node Address to the desired address and click on
Apply.
Data Rate
Cable Length (Maximum)
125KB
500 m (1600 ft)
250KB
200 m (600 ft)
500KB
100 m (300 ft)
Autobaud
See above, based on data rate of connected network