Output value - parameter 9, Output fault action - parameter 11, Output fault value - parameter 12 – Rockwell Automation 800F DeviceNet Pendant Stations User Manual
Page 34
 
4–4
Operations
Publication 800-UM001A-EN-P – June 2004
OUTPUT VALUE – Parameter 9
In normal operation, the device shall permit output to be turned on 
and off. The default for the Output Value is Output Off.
Important: If the device is connected to a master with I/O
messaging, the I/O messaging will overwrite this 
command.
OUTPUT FAULT ACTION – Parameter 11
In normal operation, the device shall permit configuration of the 
Output Fault Action. This tells the device what to do with the output 
in the case of a fault state. If Fault Value is selected, the device refers 
to parameter 12, Output Fault Value, for action on a fault. The default 
for Output Fault Value is Fault Value.
OUTPUT FAULT VALUE – Parameter 12
In normal operation, the device shall permit configuration of the 
Output Fault Value. If parameter 11, Output Fault Action is set to 
Fault Value, this parameter tells the device what to do with the output 
in case of a fault state. The default for Output Fault Value is Fault 
Output Off.
Value
Output Value
0
Output Off
1
Output On
Value
Fault Action
0
Fault Value
1
Hold Last State
Value
Fault Value
0
Fault Output Off
1
Fault Output On