OUTPUT IDLE ACTION – Parameter 13
In normal operation, the device shall permit configuration of the 
Output Idle Action. This tells the device what to do with the output in 
the case of an idle state. If Idle Value is selected, the device refers to 
parameter 14, Output Idle Value, for action on an idle state. The 
default for Output Idle Value is Idle Value.
OUTPUT IDLE VALUE – Parameter 14
In normal operation, the device shall permit configuration of the 
Output Idle Value. If parameter 13, Output Idle Action is set to Idle 
Value, this parameter tells the device what to do with the output in the 
case of an idle state. The default for Output Idle Value is Idle Output 
Off.
AUTOBAUD – Parameter 15
In normal operation, the device shall permit disabling of the 
Autobaud feature. The default value for this parameter is Enabled.
Value
Idle Action
0
Idle Value
1
Hold Last State
Value
Idle Value
0
Idle Output Off
1
Idle Output On
Value
Function
0
Enabled
1
Disabled