Class code 0x03 — devicenet object – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 66

Publication 0160-5.5 - September 1997
DeviceNet Information
B-5
Class Code 0x03 —
DeviceNet Object
Instance 1 Attributes:
➀
Allocation_byte
Bit 0
Explicit Messaging
Bit 1
Polled I/O
Bit 4
Change of state
Bit 5
Cyclic
Common Services
Class Attributes: None Supported
Number of Instances: 1
Attribute ID
Access Rule
Name
Data Type
Value
1
Get/Set
Node Address
USINT
0 to 63
2
Get/Set
Data Rate
USINT
0 to 2
3
Get/Set
BOI
BOOL
0 = Hold in error state on BOI error
1 = Reset CAN chip on BOI error
4
Get/Set
Bus-off Counter
USINT
0 to 255
5
Get
Allocation Info
Allocation Choice
Master Node Addr
Structure of:
BYTE
USINT
Allocation_byte➀
0 to 63 = Address
255 = Unallocated
8
Get
MAC ID switch value
USINT
0 to 63
9
Get
Baud Rate switch val
USINT
0 to 3
Service
Code
Implemented for:
Service
Name
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single
0x4B
No
Yes
Allocate_Master/Slave_Connection_Set
0x4C
No
Yes
Release_Master/Slave_Connection_Set