Class code 0x05 — connection object (continued) – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 68

Publication 0160-5.5 - September 1997
DeviceNet Information
B-7
Class Code 0x05 —
Connection Object (Continued)
Instance 2: Attributes (Polled I/O Message Connection)
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out
2
Get
Instance Type
USINT
1 = I/O Message
3
Get
Transport Class Trigger
USINT
0x82
4
Get
Produced Connection ID
USINT
10xxxxxx100 xxxxxx = Node address
5
Get
Consumed Connection ID
USINT
10xxxxxx101 xxxxxx = Node address
6
Get
Initial Comm Characteristics
USINT
0x21
7
Get
Produced Connection Size
USINT
0 to 8
8
Get
Consumed Connection Size
USINT
0 to 4
9
Get/Set
Expected Packet Rate
USINT
Timer resolution of 10 msec.
12
Get/Set
Watchdog Action
USINT
0 = Transition to timed out
1 = Auto delete
2 = Auto reset
13
Get
Produced Connection Path Length
USINT
3
14
Get/Set
Produced Connection Path
[63hex][hex string] where [hex string] is the
input assembly number in hex
15
Get
Consumed Connection Path Length
USINT
3
16
Get/Set
Consumed Connection Path
[63hex][hex string] where [hex string] is the
output assembly number in hex