Class code 0x05 — connection object – Rockwell Automation 160 DEVICENET (DN1) MODULE FRN 1-2.XX User Manual
Page 67

Publication 0160-5.5 - September 1997
B-6
DeviceNet Information
Class Code 0x05 —
Connection Object
Instance 1 Attributes: Explicit Message Instance
Class Attributes: None Supported
Number of Instances: 3
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
State
USINT
0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out
5 = Deferred delete (available with Commu-
nication Module version 2.00 and later)
2
Get
Instance Type
USINT
0 = Explicit Message
3
Get
Transport Class Trigger
USINT
0x83
4
Get
Produced Connection ID
USINT
10xxxxxx100 xxxxxx = Node address
5
Get
Consumed Connection ID
USINT
10xxxxxx100 xxxxxx = Node address
6
Get
Initial Comm. Characteristics
USINT
0x22
7
Get
Produced Connection Size
USINT
7
8
Get
Consumed Connection Size
USINT
7
9
Get/Set
Expected Packet Rate
UINT
Timer resolution of 10 msec.
12
Get/Set
Watchdog Action
USINT
1 = Auto delete
3 = Deferred delete (available with Commu-
nication Module version 2.00 and later)
13
Get
Produced Connection Path Length
USINT
0
14
Get
Produced Connection Path
Null (no data)
15
Get
Consumed Connection Path Length
USINT
0
16
Get
Consumed Connection Path
Null (no data)