Grounding, Short-circuit ratings, Devicenet terminals – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 24

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

25

Installation and Wiring Chapter 2

➊ An earth ground connection to this terminal will assist in obtaining compliance with Electromagnetic

Compatibility requirements.

DeviceNet Terminals

The following table defines the DeviceNet connector terminal designations.

Grounding

The following grounding recommendations are provided to ensure
Electromagnetic Compatibility compliance during installation:

• The earth ground terminal of the EC4 Current Monitoring Relay shall be

connected to a solid earth ground via a low-impedance connection

• Installations employing an external ground fault sensor shall ground the

cable shield at the sensor with no connection made at the EC4 Current
Monitoring Relay

Short-Circuit Ratings

The EC4 Current Monitoring Relay is suitable for use on circuits capable of
delivering not more than the RMS symmetrical amperes listed in the following
tables.

95/96

Trip Relay

Trip Relay

IT1/IT2

S1/S2

External ground fault sensor input

Table 7 - DeviceNet Terminal Designation

Terminal

Signal

Function

Color

1

V-

Common

Black

2

CAN_L

Signal Low

Blue

3

Drain

Shield

Non-insulated

4

CAN_H

Signal High

White

5

V+

Power Supply

Red

Table 6 - Control Terminal Designation

Terminal
Designation

Reference

Description

Table 8 - UL Short-Circuit Ratings

Cat. No.

Maximum Available Fault
Current [A]

Maximum Voltage
[V]

193-EC

_

_B

5,000

600

193-EC

_

_D

5,000

600

193-EC

_

_E

10,000

600

193-EC

_

_Z

5,000

600