Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual

Page 64

Advertising
background image

Rockwell Automation Publication 193-UM011A-EN-P - September 2010

65

Programmable Parameters Chapter 5

IN3 ASSIGNMENT

This parameter allows the user to assign a
specific function to the discrete IN3 input.

Parameter Number

85

Access Rule

Get/Set

Data Type

USINT

Object Mapping

29

hex

-1-179

Group

Advanced Setup

Units

Minimum Value

0 = Normal

1 = Trip Reset

2 = Remote Trip

3 = L1 Loss Arm

4 = L2 Loss Arm

5 = L3 Loss Arm

6 = L1 L2 Loss Arm

7 = L2 L3 Loss Arm

8 = L1 L3 Loss Arm

Maximum Value

9 = L1 L2 L3 Loss Arm

Default Value

0

IN4 ASSIGNMENT

This parameter allows the user to assign a
specific function to the discrete IN4 input.

Parameter Number

86

Access Rule

Get/Set

Data Type

USINT

Object Mapping

29

hex

-1-180

Group

Advanced Setup

Units

--

Minimum Value

0 = Normal

1 = Trip Reset

2 = Remote Trip

3 = L1 Loss Arm

4 = L2 Loss Arm

5 = L3 Loss Arm

6 = L1 L2 Loss Arm

7 = L2 L3 Loss Arm

8 = L1 L3 Loss Arm

Maximum Value

9 = L1 L2 L3 Loss Arm

Default Value

0

GF TRIP INHIBIT

This parameter allows the installer to inhibit
a ground fault trip from occurring when the
ground fault current exceeds the maximum
range of the core balance sensor
(approximately 10 A).

Parameter Number

89

Access Rule

Get/Set

Data Type

BOOL

Object Mapping

Group

Advanced Setup

Units

--

Minimum Value

0 = Disabled

Maximum Value

1 = Enabled

Default Value

0