Advanced setup group – Rockwell Automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual
Page 60

Rockwell Automation Publication 193-UM011A-EN-P - September 2010
61
Programmable Parameters Chapter 5
Advanced Setup Group
TRIP ENABLE
This parameter allows the installer to enable
or disable trip functions separately. Overload,
Phase Loss, and Comm Fault are enabled
from the factory.
1 = Enabled
0 = Disabled
Parameter Number
24
Access Rule
Get/Set
Data Type
WORD
Object Mapping
0x29-1-124
Group
Advanced Setup
Units
—
Minimum Value
0000000000000000
Maximum Value
1111111111111111
Default Value
0000000000000000
Bit
Function:
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
X
Ground Fault
X
L1 Undercurrent
X
L2 Undercurrent
X
L3 Undercurrent
X
L1 Overcurrent
X
L2 Overcurrent
X
L3 Overcurrent
X
L1 Loss
X
L2 Loss
X
L3 Loss
X
Comm Fault
X
Comm Idle
—
—
X
Remote Trip
WARNING ENABLE
This parameter allows the installer to enable
or disable warning functions separately. All
warning functions are disabled from the
factory.
1 = Enabled
0 = Disabled
Parameter Number
25
Access Rule
Get/Set
Data Type
WORD
Object Mapping
0x29-1-125
Group
Advanced Setup
Units
—
Minimum Value
0000000000000000
Maximum Value
1111111111111111
Default Value
0000000000000000