Chapter 5 Programmable Parameters
IN1 ASSIGNMENT
This parameter allows the user to assign a
specific function to the discrete IN1 input.
Parameter Number
83
Access Rule
Get/Set
Data Type
USINT
Object Mapping
29
hex
-1-177
Group
Advanced Setup
Units
—
Minimum Value
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = L1 Loss Arm
4 = L2 Loss Arm
5 = L3 Loss Arm
6 = L1 L2 Loss Arm
7 = L2 L3 Loss Arm
8 = L1 L3 Loss Arm
Maximum Value
9 = L1 L2 L3 Loss Arm
Default Value
0
IN2 ASSIGNMENT
This parameter allows the user to assign a
specific function to the discrete IN2 input.
Parameter Number
84
Access Rule
Get/Set
Data Type
USINT
Object Mapping
29
hex
-1-178
Group
Advanced Setup
Units
—
Minimum Value
0 = Normal
1 = Trip Reset
2 = Remote Trip
3 = L1 Loss Arm
4 = L2 Loss Arm
5 = L3 Loss Arm
6 = L1 L2 Loss Arm
7 = L2 L3 Loss Arm
8 = L1 L3 Loss Arm
Maximum Value
9 = L1 L2 L3 Loss Arm
Default Value
0