Wiring, Power, control, and ground wiring – Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 31
Advertising

Installation and Wiring
2-13
Wiring
Power, Control, and Ground Wiring
Table 2.1 provides the power, control, safety inputs, and ground wire
capacities, and the tightening torque requirements. The power,
control, ground, and safety monitor terminals will accept a maximum
of two wires per terminal.
Table 2.1
Power, Control, Safety Input, Ground Wire Size, and Torque
Specifications
Terminals
Wire Size
Torque
Wire Strip Length
Power
and
Ground
Primary/Secondary
Terminal:
1.5…4.0 mm
2
(#16 …#10 AWG)
Primary Terminal:
10.8 lb.-in.
(1.2 N•m)
Secondary Terminal:
4.5 lb.-in
(0.5 N•m)
0.35 in. (9 mm)
Control and Safety
Inputs
1.0 mm
2
…4.0 mm
2
(#18…#10 AWG)
6.2 lb.-in
(0.7 N•m)
0.35 in. (9 mm)