User i/o misc. group – Rockwell Automation 284G ArmorStart - User Manual User Manual
Page 68

3-14
Bulletin 280G/281G Programmable Parameters
User I/O
Misc. Group
Off-to-On Delay
This parameter allows the
installer to program a time
duration before an input is
reported “ON”
Parameter Number
30
Access Rule
GET/SET
Data Type
UINT
Group
User I/O
Units
ms
Minimum Value
0
Maximum Value
65.000
Default Value
0
On-to-Off Delay
This parameter allows the
installer to program a time
duration before an input is
reported “OFF”
Parameter Number
31
Access Rule
GET/SET
Data Type
UINT
Group
User I/O
Units
ms
Minimum Value
0
Maximum Value
65.000
Default Value
0
In Sink/Source
This parameter allows the
installer to program the inputs to
be sink or source.
0=Sink
1=Source
Parameter Number
32
Access Rule
GET/SET
Data Type
BOOL
Group
User I/
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Keypad Mode
This parameter selects if the
keypad operation is maintained
or momentary
0= Maintained
1= Momentary
Parameter Number
45
Access Rule
GET/SET
Data Type
BOOL
Group
Misc.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
Keypad Disable
This parameter disables all
keypad function except for the
“OFF” and “RESET” buttons
0=Not Disabled
1=Disabled
Parameter Number
46
Access Rule
GET/SET
Data Type
BOOL
Group
Misc.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0