3-14

Bulletin 280G/281G Programmable Parameters

User I/O

Misc. Group

Off-to-On Delay

This parameter allows the
installer to program a time
duration before an input is
reported “ON”

Parameter Number

30

Access Rule

GET/SET

Data Type

UINT

Group

User I/O

Units

ms

Minimum Value

0

Maximum Value

65.000

Default Value

0

On-to-Off Delay

This parameter allows the
installer to program a time
duration before an input is
reported “OFF”

Parameter Number

31

Access Rule

GET/SET

Data Type

UINT

Group

User I/O

Units

ms

Minimum Value

0

Maximum Value

65.000

Default Value

0

In Sink/Source

This parameter allows the
installer to program the inputs to
be sink or source.

0=Sink
1=Source

Parameter Number

32

Access Rule

GET/SET

Data Type

BOOL

Group

User I/

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Keypad Mode

This parameter selects if the
keypad operation is maintained
or momentary

0= Maintained
1= Momentary

Parameter Number

45

Access Rule

GET/SET

Data Type

BOOL

Group

Misc.

Units

Minimum Value

0

Maximum Value

1

Default Value

0

Keypad Disable

This parameter disables all
keypad function except for the
“OFF” and “RESET” buttons

0=Not Disabled
1=Disabled

Parameter Number

46

Access Rule

GET/SET

Data Type

BOOL

Group

Misc.

Units

Minimum Value

0

Maximum Value

1

Default Value

0