Bulletin 280G/281G Programmable Parameters
3-25
Overload Class
This parameter allows the
installer to select the overload
class
1= Overload Class 10
2= Overload Class 15
3= Overload Class 20
Parameter Number
107
Access Rule
GET/SET
Data Type
USINT
Group
Starter Setup
Units
xx.x Amps
Minimum Value
1
Maximum Value
3
Default Value
1
OL Reset Level
This parameter allows the
installer select the % Thermal
Capacity which an overload can
be cleared
Parameter Number
108
Access Rule
GET/SET
Data Type
USINT
Group
Starter Setup
Units
% FLA
Minimum Value
0
Maximum Value
100
Default Value
75