Rockwell Automation 1391ES AC Servo Controller User Manual

Page 10

Advertising
background image

Specifications

Chapter 2

2-8

Specifications are for reference only and are subject to change without notice.

Environmental Specifications

The 1391B-ES must be mounted in an enclosure that is clean, dry and
ventilated by filtered or cooled air. Enclosures vented with ambient air
must have appropriate filtering to protect against contamination caused by
oils, coolants, dust, condensation etc. The ambient air temperature must be
kept between 0 to 60

°

C (32 to 140

°

F) and the humidity between 5 and

95%, non-condensing.

The 1391B-ES is equipped with an integral cooling fan. The general flow
of air through the unit must be maintained by following the recommended
spacing guidelines found in Chapter 6. The 1391B-ES can operate at
elevations to 3300 feet (1000 meters) without derating, however, the
current rating must be derated by 3% for each additional 1000 feet (305
meters) up to 10,000 feet (3050 meters). Consult with your local
Allen-Bradley Sales Representative prior to operation over 10,000 feet
(3050 meters).

Controller Power Dissipation

The 1391B-ES dissipation characteristics are approximated in Table 2.A.

Table 2.A
Controller Power Dissipation

Rated Power
Output
(%)

20

40

60

80

100

1391B-ESAA
15
(watts)

38

76

114

152

190

1391B-ESAA
22
(watts)

55

110

165

220

275

1391B-ESAA
45
(watts)

104

208

312

416

520

Transformer Power Dissipation

The power dissipation characteristics of the 1391 Isolation Transformer are
shown in Table 2.B.

Table 2.B
1391 Isolation Transformer Power Dissipation

Rated Power
Output
(%)

20

40

60

80

100

1.5kV
A
(watts)

13

25

38

50

60

3.5kV
A
(watts)

35

70

105

140

175

5.0kV
A
(watts)

50

100

150

200

250

10.0kV
A
(watts)

100

200

300

400

500

12.5kV
A
(watts)

125

250

375

500

625

15.0kV
A
(watts)

150

300

450

600

750