Rockwell Automation 1391ES AC Servo Controller User Manual
Page 47

Start-Up
Chapter 7
7-45
o
3.
Assure that preliminary adjustment of the following items has been
performed:
- Potentiometer adjustments as described in Chapter 5.
- S1, S2 and SW1 switch settings as described in Chapter 5.
Important: The above adjustments must be performed before
proceeding.
o
4.
Assure that the controller circuit breaker (MCB) OFF.
o
5.
Apply power to the transformer, but Do Not enable the controller or
energize the line/DB contactor (M).
o
6.
Using a voltmeter, verify that the voltages listed below are present at
the locations shown. The tolerance for all voltages is
±
10%. Clear
faults before replacing any blown fuses.
Location
Voltage
TB5-4 to TB5-5
230V AC
TB5-4 to TB5-6
230V AC
TB5-5 to TB5-6
230V AC
TB4-19 to TB4-20
18V AC
TB4-21 to TB4-20
18V AC
TB4-21 to TB4-19
36V AC
TP13 to TP12
+12V DC
TP14 to TP12
–12V DC
o
7.
Remove all power to the transformer.
o
8.
The wires connected to terminals 9 and 10 of TB2 must be marked
and removed to allow for local operation of the Enable circuit.
Connect a suitable temporary switch between these terminals and
insulate the switch connections. See Figure 7.1.
Figure 7.1
Local Control Connections
Temporary
Local Enable
Switch
Variable
Command
Input
Battery
Box
1391B-ES
Controller
TB2-1
TB2-2
TB2-9
TB2-10
+
–