Node adjustment, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T Function Block Prog. Manual, Series A/B User Manual
Page 152: Write block link

5–36
Block Transfer Services
1336 FORCE — 5.9 August 1995
The Write Block Link message writes the link information for an
entire block.
PLC Block Transfer Instruction Data
BTW Instruction Length:
36 Words
BTR Instruction Length:
4 Words
0
Header
Word 1
Header
Word 1
8F06
80ID
PLC Decimal Value
0F06 –– Message OK
Parameter Number
8F06 –– Message Error
Message Structure
Header
Word 2
Data
Word 3
Header
Word 2
Header
Word 3
0
PLC Request –– Block Transfer Write
Drive Response –– Block Transfer Read
Packet Number 0
Data
Word 4
Node 0 Source
Node 0 File Number
Data
Word 5
Data
Word 6
•
Node 15 Source
Data
Word 35
•
•
•••
Node 1 Source
Node 1 File Number
Data
Word 7
Data
Word 8
Node 15 File Number
Data
Word 36
ID = block ID number
Hex
Hex
80ID
Status Word
Header
Word 4
Message Operation
The Write Block Link message writes the output parameter to the
input parameter. The data words contain the packet number and up
to 15 source nodes. The buffer must always be padded with zeros if
32 nodes are not being written.
If the service encounters any invalid output references, the drive
stops processing the service and returns an error.
Node Adjustment:
Write Block Link