1–18
Getting Started
1336 FORCE — 5.9 August 1995
— Enter the 3rd Value at the Function Block Node
BTW
Data File
N57:0
0000
8F01
8003
7FFF
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
7. Set the Multiplexer block Input 1 value (block 3, node 0) to
7FFF
hex
= 32767
dec
.
8. Toggle bit I:00/00 to initiate the block transfer routine which
downloads the node value.
9. Verify that the write was successful. If N57:101 = 0F01
hex
(Block
Transfer Read data), there are no errors.
— Enter the 4th Value at the Function Block Node
BTW
Data File
N57:0
0000
8F01
8103
8001
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
10.Set the Multiplexer block Input 3 value (block 3, node 1) to
8001
hex
= – 32767
dec
.
11. Toggle bit I:00/00 to initiate the block transfer routine which
downloads the node value.
12.Verify that the write was successful. If N57:101 = 0F01
hex
(Block
Transfer Read data), there are no errors.
— Enter the 5th Value at the Function Block Node
BTW
Data File
N57:0
0000
8F01
8304
FFFF
0
0
0
0
0
0
0
1
2
3
4
5
6
7
8
9
13.Set the Rate Limit block Rate value (block 4, node 3) to FFFF
hex
= 65535
dec
.
14.Toggle bit I:00/00 to initiate the block transfer routine which will
download the node value.
15.Verify that the write was successful. If N57:101 = 0F01
hex
(Block
Transfer Read data), there are no errors.