Function Block Library
4–19
1336 FORCE — 5.9 August 1995
FILTER
BLOCK TYPE 8 decimal 8 hexadecimal
Filter
ID =
Exec =
Out
NODE 0
In
NODE 1
Rad /S
NODE 2
DEFINITION
A first order low pass algorithmic filter with a programmable
bandwidth in increments of .1 radians/second.
INPUTS
In — The signed integer to be filtered.
Rad/S — The bandwidth in .1 radians/second, with a maximum
value of 400 (40 radians).
OUTPUT
Out — A signed, filtered, output integer that is clamped to
±
32767.
FUNCTION
If Rad/S = 0, then Out = In.
If Rad/S
≠
0, then Out = Out
I–1
+ k(In – Out
I–1
).
PARAMETERS
DATA TYPE
LINKABLE
DEFAULT VALUE
RANGE
In
Signed Integer
Yes
0
±
32767
Rad/S
Unsigned Integer
No
0
0 to 400
Out
Signed Integer
No
—
±
32767
Example 1 — (10) Radians-per-Second — Horizontal Scale = 100 mS/Division
" 1 Time A
Constant
≈
63%
≈
100 mS
+ 32767
"
– 32767
"
FILTER In
"
A––– 3 Time Constants –––"
≈
96%
≈
300 mS
A FILTER Out