1–11
Getting Started
1336 FORCE — 5.9 August 1995
Step 6 — Check Links
Once all function blocks and their links have been established, node
connections in the program should be validated by using a
Check
Node Connections
command from the
Function Blocks
pull-down menu. This function is performed by the
DriveBlockEditor, not the drive.
If all links are correct, the following display will be shown.
If any errors were made, a Connection Errors Dialog Box will detail
the errors.
Step 7 — Download the Program
Once the links have been checked, the execution list must be
downloaded to the drive to enable the function block program.
1. Select the
Download to Drive
option from the
DriveBlockEditor’s pull-down
Drive
menu. If you know the
station number, enter it at this time. If the Station number is
unknown, use the
WHO
menu option shown below to scan for
active DH+ stations.
2. During the download process, the drive checks function block
links and node values. A message will appear telling you whether
the download was successful.