Parameter Table

Parameter 580 – [A> Timer 1]

Use: Specifies the timing value of timer 1.
Program Terminal Units: Seconds
Maximum Value: 2.0
Minimum Value: 2.0
Default Value: 2.0
NOT CHANGEABLE

Description: This parameter specifies the amount of time in seconds
required for Timer T1 in the Logic State Machine to time out. The
default time is 2.0 seconds.

Parameter 581 – [A> P/I Regulator Integral Channel High
Clamp]

Use: Specifies the maximum value of the integral term
Program Terminal Units: None
Maximum Value: 50
Minimum Value: 0
Default Value: 25

Description: This parameter specifies the maximum value that the
integral channel can operate to.

Parameter 582 – [A> P/I Regulator Integral Channel Low
Clamp]

Use: Specifies the minimum value of the integral term
Program Terminal Units: None
Maximum Value: 0
Minimum Value: -50
Default Value: -25

Description: This parameter specifies the minimum value that the
integral channel can operate to.

Parameter 583 – [A> P/I Regulator Output High Clamp]

Use: Specifies the maximum value of the P/I Output.
Program Terminal Units: None
Maximum Value: 500
Minimum Value: 0
Default Value: 160

Description: This parameter specifies the minimum value that the P/I
Regulator can operate to.