Rockwell Automation 1395 Digital Reference Adapter for RTP Applications User Manual

Page 64

Advertising
background image

Publication 1395-RTP-5.2 - September 1997

8-22

Parameter Table

Parameter 593 – [A> Digital Out 4]

Use: Maps Digital Output 4
Program Terminal Units: None
Maximum Value: 16
Minimum Value: 0
Default Value: 16

Description: This parameter has a range of 0 to 16. When the
parameter is set to 16 (the default), the output bit is permanently
assigned to the State Machine Logic. The State Machine Logic
communicates with the main control board through configuration
parameter 450. The output digital logic software will determine the
output conditions for this output when this parameter is set to 16.
When the parameter is set to any other value, the output will follow
that of the Configuration Parameter. When the bit is set (ie. equal to
1), the corresponding solid state output is at 24V DC or high. Digital
output #4 at Terminal TB3-57 is normally not used.

Parameter 594 – [A> Digital Out 5]

Use: Maps Digital Output 5
Program Terminal Units: None
Maximum Value: 16
Minimum Value: 0
Default Value: 16

Description: This parameter has a range of 0 to 16. When the
parameter is set to 16 (the default), the output bit is permanently
assigned to the state machine logic which communicates with the main
control board through Configuration Parameter 450. The output digital
logic software will determine the output conditions for this output when
this parameter is set to 16. When the parameter is set to any other value,
the output will follow that of the configuration parameter. When the bit
is set (ie. equal to 1), the corresponding solid state output is at 24V DC
or high. Digital output #5 at Terminal TB3-58 is normally not used.

Parameter 595 – [A> Anal 1 Raw Out]

Use: Maps A/D Out of Anal 1
Program Terminal Units: None
Maximum Value: 0
Minimum Value: 0
Default Value: 0
READ ONLY PARAMETER

Description: This parameter is used as a monitoring device only. The
parameter is monitoring the analog #1 output of the analog to digital
converter prior to the internal digital offset and scaling constants
being applied to the channel.

Advertising