Chapter 2

Installation

In addition, the top-mounted wireway sections must be bolted together using the
provided 1/4” hardware (torque to 66 lb-in [7.5 N-m]). See

Figure 3

for typical

fastening locations and hardware arrangement

Figure 3 - Mechanical Interconnections.

Electrical Interconnections

The “DySC 400A Module” MegaDySC cabinets and the Automatic Bypass
(ABP) Switchboard are shipped separately. The customer is responsible for
system mounting. All interconnecting power cables are provided and will be
connected by a factory-trained technician during commissioning. At
commissioning the main cables will be routed from the MegaDySC cabinets to
the appropriate ABP switchboard busbar terminals via the overhead wireway. A
control wiring harness is also provided in the ABP and must be connected to the
MegaDySC cabinets. Finally, the incoming electrical service and outgoing load
cables are brought in through the top (or bottom) of the ABP switchboard and
connected to the appropriate bus locations, as shown in

Figure 4

. AC input is

WARNING: Equipment must be earth-grounded according to local and
national electric codes. Failure to supply proper equipment grounding
may result in electrical shock or death. All interconnection wiring
must be installed by a qualified electrician in compliance with the
National Electrical Code standards.