Remote seamless bypass command operation – Rockwell Automation 1608M MegaDySC User Manual, 800 - 2400 A User Manual
Page 16

16
Rockwell Automation Publication 1608M-UM002A-EN-P - September 2013
Chapter 3
Communications
Conditions that will automatically close the Bypass Circuit Breaker (CBB) are
the last five rows of
Remote Seamless BYPASS Command Operation
A normally-open PLC contact, relay contact, or push-button contact may be
connected between TB1/14 and TB1/15. Close the contact to initiate an
automatic seamless bypass operation: CBB will close, then CBI and CBO will
open, removing power from the MegaDySC cabinets; voltage sag correction will
then be disabled.
This feature may be utilized as an Emergency Power Off (EPO) function for the
MegaDySC cabinets only. Power to the output loads or output distribution
panel, if present, will not be interrupted. Note that the automatic bypass
functionality requires that nominal AC power is present at the switchboard input
terminals.